8.
Utilizing the arrow pushbuttons, select the Paralleling Type to be "MASTER/
FOLLOWER", then press the ENT pushbutton.
9.
Press the Down arrow pushbutton once, the "Master/Follower" screen will be
displayed.
10. Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Master/Follower
NONE C
11. Utilizing the arrow pushbuttons select "FOLLOWER", then press the ENT
pushbutton.
12. Press the Down arrow pushbutton once, the "Paralleling Address" screen will be
displayed.
The Master P aralleling Address must be the highest address in the network. All
Follower addresses must be a value less than the Master.
The control’ s position in the paralleling network is determined by its paralleling
address. As shown in
, Position 1 should be assigned a paralleling address
of 1, Position 2 a paralleling address of 2 and so on, in an ascending order. In this
example the Master control will be in Position 8 with a Paralleling Address of 8.
13. Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Paralleling Address
16 C
14. Utilizing the arrow pushbuttons, enter the desired Paralleling Address (1 to 16) then
press the ENT pushbutton.
15. Press the Down arrow pushbutton once, the "Num. Devices" screen will be
displayed.
Number of De vices is the number of total devices that are in the paralleling scheme
(maximum 16 inclusive of the Master).
16. Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Num. Devices
2 C
17. Utilizing the arrow pushbuttons, enter the total Number of Devices then press the
ENT pushbutton.
18. Press the Down arrow pushbutton once, the "T.P.R. Timeout" screen will be
displayed.
The Tap Position Response Timeout is the time within which the Followers have to
be at the same tap position as that of the Master (Range 1000 to 60000 ms).
If the Tap Position Response Timeout is greater than the Intertap Delay setting, then
the Tap Position Response Timeout is used as the Intertap Delay, so that the Master
waits for all the Followers to make a tapchange before the Master takes the next tap.
19. Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
T.P.R. Timeout
Section 6
1VAC388793-MB A
Configuration
426
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......