GUID-53E63F94-8E89-48E6-8C7D-3CB55622B3C2 V1 EN
Figure 347:
Delta VAr Peer to Peer Paralleling Configuration Tool Dialog Screen
6.3.3.1
Bus topology
Bus configurations are processed to divide the main paralleling group into several sub
groups. The algorithm that is used to accomplish this task is called the Grouping Operation
Algorithm (GOA).
The basic bus configurations supported are Single Bus, Ring Bus and Double Bus. In
addition to obtaining VArs or load Current information through communication, this
method has the capability to recognize which transformers are still in parallel in the event
of tiebreakers or switches being opened or closed. Depending on the bus configuration,
each control monitors 1 Line Breaker and 1 or 2 Tie Breakers.
A means to make commissioning of the paralleling system easier, TCC600 provides a
feature to detect all ABB controls that form part of the parallel network. After detection
of the controls, depending on the bus configuration selected, the user can view the
paralleling network as a whole and also individually configure each control.
Single bus
A Single Bus with eight transformers is shown in
1VAC388793-MB A
Section 6
Configuration
TCC300
431
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......