GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 369:
Save to Device Confirmation Screen
6.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to the Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 370:
Setpoints Successfully Written To The Control Dialog Screen
7.
If a neutral tap position contact is connected to the control, run the regulator to the
neutral tap position as indicated on the regulator.
The control will recognize the neutral contact/light signal and set the tap position
accordingly.
6.4.1.13
Setting Highest and Lowest Tap from the HMI
This setting is applicable to Reg External #1 and #2, and XFMR External
#1, #2 and #3, modes of Tap Information.
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the "Tap
Settings" menu.
Section 6
1VAC388793-MB A
Configuration
468
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......