GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 381:
Save to Device Confirmation Screen
4.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to the Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 382:
Setpoints Successfully Written To The Control Dialog Screen
6.5.2
Harmonics setup
The Harmonics Calculation feature provides the user with the ability to set predefined
harmonic voltage and current thresholds (individual, voltage percent from 0 to 30%,
current percent from 0 to 100%) for the selected harmonics. Current Threshold includes
a minimum Current Threshold setting from 0 to 200 mA. Also, a common delay setting
from 1 to 10 seconds is available.
The Harmonic voltage and/or current threshold Pickup and Dropout can be selected as
inputs to trigger the Oscillograph Recorder. The Harmonic voltage/current Pickup or the
voltage/current Dropout can be selected to trigger the Sequence of Events Recorder.
6.5.2.1
Setting the Active Harmonics Inputs to the Oscillograph and Sequence of
Events Recorders from the HMI
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
1VAC388793-MB A
Section 6
Configuration
TCC300
479
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......