6.5.2.3
Setting the Harmonic Voltage and Current Threshold Delay from the HMI
This delay setting applies to both the Voltage Threshold and the Current
Threshold.
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, until "Harmonics Setup" is
displayed.
4.
Press the Down arrow pushbutton, as necessary, until the "Harmonic Alarm Delay"
setting screen is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Harmonic Alarm Delay
1 s C
6.
Utilizing the Up/Down arrow pushbuttons, enter the desired Threshold Delay value
from 1 to 10 Seconds, then press the ENT pushbutton.
6.5.2.4
Setting the Active Harmonics Inputs to the Oscillograph and Sequence of
Events Recorders from TCC600
1.
Select
Setup/Harmonics Setup
from the TCC600 toolbar. TCC600 will display the
Harmonics Setup dialog screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
481
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......