5.
Press the ENT pushbutton. If prompted, enter a valid Level Access Code. The
following will be displayed:
LDC Selection
RX C
6.
Utilizing the Up/Down arrow pushbuttons, select the desired type of Line Drop
Compensation (RX or Z), then press the ENT pushbutton.
7.
Depending on the selection, proceed as follows:
•
If "RX" Line Drop Compensation was selected, proceed to "Setting LDC
Resistance (R) and Reactance (X) Values".
•
If "Z" Line Drop Compensation was selected, proceed to "Setting LDC-Z" .
7.4.2
Setting Power Flow Forward and Power Flow Reverse LDC
Resistance (R) and Reactance (X) values from the HMI
The steps necessary to set the Power Flow Forward LDC Resistance (R)
and Reactance (X) values are described here. The steps to set the Power
Flow Reverse LDC Resistance (R) and Reactance (X) are similar.
1.
Press the Up Arrow (SETP Hot Button) pushbutton to wake the unit. The menu will
advance to "SETPOINTS".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Profile Settings
3.
Press the Right or Left arrow pushbuttons, as necessary, to navigate to the "Common
Settings" menu.
Editing Setpoints in the wrong Setpoint Profile can cause the control
to operate incorrectly.
4.
Verify that the desired Setpoint Profile is indicated, then press the Right or Left
arrow pushbutton, as necessary, to navigate to the "Power Flow Forward" menu.
5.
Press the Down arrow pushbutton, as necessary, to navigate to the "LDC R Fwd" (or
LDC R Rev) menu item.
6.
Press the ENT pushbutton. If prompted, enter a valid Level Access Code. The
following will be displayed:
LDC R Fwd
0 Volts C
The double directional arrows in the display indicate that by
pressing Right or Left arrow pushbuttons the display will jump to the
LDC Selection display in the Common Settings menu. Pressing any
1VAC388793-MB A
Section 7
Setpoints
TCC300
517
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......