Distributed Generation
•
Auto Determination
•
Auto Determination (Measured)
Selecting "Save" saves all profiles to the control.
4.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 422:
Save to Device Confirmation Screen
5.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 423:
Setpoints Successfully Written To The Control Confirmation
Screen
7.7
Power flow settings
Bandcenter
The center of the voltage band is adjustable from 100.0 to 135.0 Vac in 0.1 volt increments
(for example, 120.0 Vac).
1VAC388793-MB A
Section 7
Setpoints
TCC300
533
User Manual