If desired, select "Disable on Reverse Power".
•
Enter a Forward Power Maximum 3 Phase Capacitor Bank Size (4 to 12,000
kVAr)
•
Enter a Reverse Power Maximum 3 Phase Capacitor Bank Size (4 to 12,000
kVAr)
•
Lead % Bank Size Pickup (10 to 100%)
•
Lag % Bank Size Pickup (10 to 100%)
•
VAr Bias Voltage Step (0.1 to 2.0 V)
•
Max VAr Bias Duration (10 to 1440 min)
4.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 432:
Save to Device Confirmation Screen
5.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 433:
Setpoints Successfully Written To The Control Confirmation
Screen
Section 7
1VAC388793-MB A
Setpoints
544
TCC300
User Manual