GUID-048D237F-43CD-4AD9-AE34-E622A23E6616 V1 EN
Figure 435:
Setpoints Dialog Screen With Linear VAr Bias Enabled
3.
Enter the desired settings for the following:
•
If desired, select "Disable on Reverse Power".
•
Enter a Current Multiplier Base Value (0 to 32600)
•
Enter a "No Voltage Reduction" Linear Voltage Bias (-X) setting (-72 to 0
Volts at 200 mA Reactive Load)
•
Enter a "No Voltage Reduction" Linear Voltage Bias (-X) Limit setting (-5.0
to 0.0 Volts).
•
Enter a "During Voltage Reduction" Linear Voltage Bias (+X) setting (0 to 72
Volts at 200 mA Reactive Load)
•
Enter a "During Voltage Reduction" Linear Voltage Bias (+X) Limit setting
(0.0 to 5.0 Volts).
4.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 436:
Save to Device Confirmation Screen
5.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to Control"
confirmation screen.
Section 7
1VAC388793-MB A
Setpoints
548
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......