10.2
HMI Screen Review
10.2.1
Monitor
10.2.1.1
Metering
Load Voltage
XXX.X Volts
Displays the real-time measured value of voltage at the regulator or the transformer,
including the voltage reduction if applicable and any corrections made using the user-
selected VT correction voltage.
Meter Out Voltage
XXX.X Volts
Displays the measured voltage at the terminals of the TCC300 without any software
modifications. Used as the base for normalizing voltage.
Source Voltage
XXX.X V
(Calculated/Measured/disabled)
•
Calculated – Displays the real-time calculated source voltage-only applicable in
regulator control applications and includes any corrections made using the user-
selected VT correction voltage.
•
Measured – Displays the real-time measured source voltage when Reverse Power is
detected and Reverse Power Operation is "Regulate Rev Measured".
Load Current
x.x mA LEAD/LAG
Displays the real-time measured value of load current related to the scaling factor Current
Transformer of 200 mA.
Circulating Current
x.x mA LEAD/LAG
Displays the representable value of circulating current, if the control is used with
M-0115A Parallel Balancing Module or equivalent. Displays the value of DVAr Current
when DVAr Paralleling method is enabled.
1VAC388793-MB A
Section 10
Appendix A HMI
TCC300
603
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......