Allows one of three methods to be used for the control to switch between forward/reverse
power operation. The three settings are None, Forward Bias, and Reverse Bias.
10.2.2.3
Power Flow Forward
Bandcenter Fwd
XXX.X Volts
Forward power bandcenter is adjustable from 100.0 V to 135.0 V in 0.1 V increments with
a factory setting of 120.0 V.
Bandwidth Fwd
X.X Volts
Forward power bandwidth is adjustable from 1.0 V to 10.0 V in 0.1 V increments with a
factory setting of 2.0 V.
LDC RES-REAC
LDC R Fwd ← →
X Volts
Forward power Line Drop Compensation resistance is adjustable from -72 V to +72 V in
1 V increments with a factory setting of 0 V.
LDC X Fwd
X Volts
Forward power Line Drop Compensation reactance is adjustable from -72 V to +72 V in
1 V increments with a factory setting of 0 V.
LDC-Z
LDC-Z Fwd ← →
X Volts
Adjustable from 0 to 72 volts in 1 volt increments.
DEFINITE DELAY
Definite Delay Fwd ← →
XX Sec
1VAC388793-MB A
Section 10
Appendix A HMI
TCC300
615
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......