Forward power time delay for a tapchange is adjustable from 1 sec. to 360 sec. in 1 second
increments with a factory setting of 30 sec.
INVERSE DELAY
Inverse Delay Fwd ← →
XX Sec
Forward power inverse delay for a tapchange is adjustable from 1 sec. to 360 sec. in 1
second increments with a factory setting of 30 sec.
10.2.2.4
Power Flow Reverse
Bandcenter Rev
XXX.X Volts
Reverse power bandcenter is adjustable from 100.0 V to 135.0 V in 0.1 V increments with
a factory setting of 120.0 V.
Bandwidth Rev
X.X Volts
Reverse power bandwidth is adjustable from 1.0 V to 10.0 V in 0.1 V increments with a
factory setting of 2.0 V.
LDC RES-REAC
LDC R Rev ← →
X Volts
Reverse power Line Drop Compensation resistance is adjustable from -72 V to +72 V in
1 V increments, with a factory setting of 0 V.
LDC X Rev
X Volts
Reverse power Line Drop Compensation reactance is adjustable from -72 V to +72 V in
1 V increments, with a factory setting of 0 V.
LDC-Z
LDC-Z Rev ← →
X Volts
Section 10
1VAC388793-MB A
Appendix A HMI
616
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......