the Counter contact input of the TCC300. The counter will increment when the counter
input sees the cam follower open and then close.
Cooper Quick Drive
disable
Enable this setting when using a Cooper Quick Drive regulator. For Cooper Spring Drive
and Direct Drive, this setting should be disabled.
Cam Follower
disable
Enables or disables the Cam Follower feature.
X Mode Delay
XX ms
When the control is using 1X or 2X Mode counter contact detection method, the X Mode
Delay setting in milliseconds can be used to delay the detection of the NEUTRAL position
switch.
Counter Time Window
0.5 Sec
When the control is using Count Window Mode counter contact detection method, the
counter time window may be set from 0.0 to 60.5 Seconds with a default setting of 0.5.
Op Counter Preset
XXXXXX
The counter cannot be reset, but can be preset to any value up to 999,999 in the Tap
Settings menu.
Ntrl Counter Preset
XXXXXX
Preset the Neutral Counter to any value up to 999,999.
Lower Counter Preset
XXXXXX
Either preset or reset the lower counter.
Section 10
1VAC388793-MB A
Appendix A HMI
624
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......