2 mS
This time delay improves robust operation when communication lines are intermittent.
Communication dead-sync time is the time that the control will wait from the last received
character and continue without attempting to resynchronize. Factory setting is 2 msec;
range is 0-32000 msec.
Output Pulse
1.5 Sec
Adjustable from 0.2 to 12 seconds in 0.1 second increments. Factory set at 1.5 seconds.
Comm Access Security
disable
When enabled, establishes Level Access security for MODBUS® communications
regardless of physical connection.
Comm Access Timeout
60 sec
Establishes the duration at which time communications will be closed with the control
when no communication activity is sensed.
TX Delay
10 ms
Delay transmission of a response of a Serial Bus (RS-232, RS 485 or Fiber Optic).
Heartbeat Option
Disabled
Toggles between five modes of operation: LTC (DNP), Regulator (DNP), Profile
Switching (DNP), Profile Switching (GOOSE) and Disabled.
10.2.5.2
Memory Card
Load Setpoints
Press ENT to begin
Load setpoint files (Unit or Master) from a Smart Flash SD Card into the unit.
Save Setpoints
1VAC388793-MB A
Section 10
Appendix A HMI
TCC300
643
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......