Serial RS232
Protocol
MODBUS
[MODBUS]
DNP3
Baud Rate
300
600
1200
2400
4800
9600
19200
38400
57600
115200 [115200]
Parity
NONE [NONE]
EVEN
ODD
Stop Bit
1
2 [2]
Sync Time
1 to 5000 [50] max 5000 ms
(_______________)
Ethernet
Auto Negotiation
Disable
Enable [Enable]
DHCP Protocol
Disable
Enable [Enable]
IP Address [0.0.0.0]
(_______________)
Net Mask [0.0.0.0]
(_______________)
Gateway [0.0.0.0]
(_______________)
Keepalive Time
1 to 50,000 (Sec) [7200]
(_______________)
Port
MODBUS® Port
0 to 65,535 [502]
(_______________)
DNP3.0 Port
0 to 65,535 [20000]
(_______________)
Network Time Synchronization
SNTP
Disable [Disable]
Enable
SNTP Server Name
(_______________)
SNTP Server Address [X.X.X.X]
(_______________)
Time Zone [GMT -5 Hr]
(_______________)
Change Communication Address
Communication Address
DNP Address
1 to 65519 [1]
(_______________)
Modbus Address
(_______________)
Substation
Table continues on next page
1VAC388793-MB A
Section 11
Appendix B Setpoint, Configuration and Communication Record Forms
TCC300
669
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......