TimeStamp
A Time Stamp is included in the report if the "TimeStamp" bit is set to true. This parameter
tells the time at which the report was generated.
DataSet
Data Set is included in the report if the "DataSet" bit is set to true. The dataset reference
shall be included in the report and derived from the member of the dataset.
ReasonCode
A Reason Code is included in the report if the "ReasonCode" bit is set to true. The report
will contain the trigger option that is responsible for generation of the report.
DataReference
Data Reference is included in the report if the "DataReference" bit is set to true. It shall
contain the Functional Constraint Data (FCD) of the data attribute values included in the
report.
EntryID
An Entry ID is included in the report if the "EntryID" bit is set to true. This parameter
represents OCTET string which is used to identify the sequence of events in a buffered
report control block.
Configuration Revision
It is included in the report if the "Configuration Revision" bit is set to true. This parameter
shall contain the corresponding attribute ConfRev of the referenced BRCB.
Buffer Overflow
The Buffer Overflow is included in the report if the "Buffer Overflow" bit is set to true. It
indicates to the client that a buffer overflow has occurred. The buffered report control
block will set this bit in the first report after the events that occurred after the overflow. The
second report will have it set to zero again.
GOOSE (Generic Object Oriented Substation Events)
GOOSE data is directly transmitted on a publisher - subscriber mechanism bases on
multicast MAC addresses. Since it is a connectionless network layer protocol, in order to
guarantee message delivery, a retransmission scheme is employed.
GOOSE Message Retransmission Timing After Initial GOOSE Message
1. Retransmit after 2 ms with TAL = 2
2. Retransmit after 4 ms with TAL = 4
3. Retransmit after 8 ms with TAL = 8
Section 13
1VAC388793-MB A
Appendix D IEC 61850 Configuration Editor
686
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......