11.1. A block of all automatic and remote operations is activated, leaving the Control
state unchanged.
11.2. All ongoing operations are terminated.
11.3. All setpoints and calibration data is backed up into internal data flash memory.
The update process, from erasing the Program Flash to complete
reprogramming takes approximately 15 seconds. Any error or loss of
power after the flash has been erased will be fatal to the control.
12. The flash programming is initiated as follows:
12.1. The entire Program Flash is erased.
12.2. The new firmware is burned into the program flash.
If for any reason the erasing or programming of the Program Flash is unsuccessful,
then the Control will terminate the update process and return to normal program
execution without rebooting.
The Control will also notify the REFU Utility by sending the appropriate error
message when queried. This type of error can result in the Program Flash not being
completely programmed. Therefore, the user should retry to update the firmware
again. A power loss in this condition will result in the Control not being able to reboot
properly.
13. When the burning of the firmware into the program flash has been completed, the
Control will Reboot.
14. When the Control has completed the reboot process, the Control will commence
normal operation subject to the previously saved setpoints and calibration data.
15. After the Control has completed its rebooting process the REFU Utility will reopen
a TCP connection on port 62000 and query for the firmware version number.
16. If the queried version number does not match the programmed version number, the
REFU Utility application will notify the user of the status of the process and allow the
user to repeat the update if desired.
17. If the queried version number matches the programmed version number, the
programming process has been successful.
15.5
Updating data file remotely
To remotely update selected data files of a control or a series of controls on an ethernet
network proceed as follows:
1.
Verify that the following conditions exist:
Section 15
1VAC388793-MB A
Appendix F Remote Ethernet file update utility
700
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......