VA
Displays the calculated primary quantity based on the user-selected voltage and current
multipliers, VT configuration (line-to-ground or line-to-line), singlephase or three-phase,
and measured secondary voltage and current.
3.6.3
Remote voltage bias
Voltage
Displays the Remote Voltage value provided to the control utilizing either DNP 3.0,
MODBUS or IEC 61850 protocols. If a voltage value is present the control is utilizing the
Remote Voltage Bias Voltage to control.
3.6.4
Secondary metering status
Load Voltage
Displays the real-time measured value of voltage at the Tapchanger and includes any
corrections made using the user-selected VT correction voltage.
Meter Out Voltage
Displays the measured voltage at the terminals of the TCC300 without any software
modifications. Used as the base for normalizing voltage.
Source Voltage
Displays the real-time calculated/measured source voltage and includes any corrections
made using the user-selected VT correction voltage.
Compensated Voltage
Displays the calculated voltage at the "load center".
Normalizing Voltage
Displays the result of the Normalizing Multiplier (0.80 to 1.20) times the Meter Out
Voltage.
Load Current
Displays the real-time measured value of current.
Power Factor
Displays the real-time calculated value of power factor.
Section 3
1VAC388793-MB A
Operation
68
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......