Figure 54:
Programmable Alarms Dialog Screen
2.
From the Low Current Block Reset section of the dialog screen select Reset.
3.24
Motor seal-in failure alarm/block
When Motor Seal-in is selected in the control the Motor Seal-in Failure Alarm/Block
feature and the input to the Abnormal Tap Position alarm are enabled by default. The user
may choose to disable the Motor Seal-in Block feature. However, the input to the
Abnormal Tap Position alarm and the Motor Seal-in Failure Alarm is always enabled
when Motor Seal-in is selected. The feature includes the following:
Abnormal Tap Position Alarm Input - The Motor Seal-in Failure Block feature provides
an input to the "Abnormal Tap Position" alarm. This input is actuated on the first
occurrence of a tapchange coincident with no motor seal-in current detected for 15
seconds.
1VAC388793-MB A
Section 3
Operation
TCC300
113
User Manual