GUID-F94E7F6F-8790-48D5-8849-51B45512FDBC V1 EN
Figure 121:
Reverse Power Vendor Cross Reference Table
4.10.5.4
Configuration
Table 27:
Primary
Item
Description
Voltage Multiplier
Adjustable from 0.1 to 3260.0 in 0.1 increments with
a factory setting of 60.0. User selection must include
knowledge of VT ratio and sensing VT-ratio
correction.
Voltage Source Multiplier
Adjustable from 0.1 to 3260.0 in 0.1 increments with
a factory setting of 60.0. User selection must include
knowledge of source VT ratio and sensing source
VT-ratio correction.
Current Multiplier
Adjustable from 1 to 32600 in 1 increments with a
factory setting of 6000. User selection must include
knowledge of CT ratio, from primary rating to 0.2 A
rating of control.
Primary Power Display
Toggles between two modes of operation: Single-
Phase – based on measured inputs, and Three-
Phase – based on measured inputs and presumed
balanced system. Factory setting is single-phase.
Section 4
1VAC388793-MB A
TCC600
184
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......