35
Max output
(charging)
current (A)
Typical circuit
breaker (A)
Typical line wire
specifications
(AWG)
Supported
by included
mechanical lug
Supported by
included cold
pressed ring
terminal
Typical PE wire
specifications
(AWG)
Supported by
included cold
pressed ring
terminal
10
13
12
12
16
20
10
12
24
30
8
8-2
10
32
40
8
8-2
10
40
50
6
8-2
6
8
8
48
60
6
8-2
8
8
56
70
4
8-2
8
8
64
80
4
8-2
8
8
80
100
2
8-2
2
8
8
Requirements
Specifications
Dedicated upstream protection device(s)
Breaker
EVSE internal Ground Fault Protection
20 mA AC
Upstream overcurrent protection breaker
Breaker rating see table above
Tripping characteristics: type C
—
Circuit breaker rating
Note:
Consult with a licensed contractor, licensed electrician, or trained installation expert to ensure compliance
with local building and safety standards.
Note:
The breaker value depends on the diameter and the length of the cable, the EVSE rating, and the
environmental parameters (for the electrician to decide).
The breaker serves as the main disconnect switch to the EVSE.