4
ABB i-bus
®
EIB / KNX
2 Device
technology
2.1 Technical
data
Device technology
Operating voltage:
– Mains voltage
90...265 V AC, 50/60 Hz
– Auxiliary voltage
10...30 V DC
– Power consumption
max. 2.8 W at 230 V AC
max. 2.0 W at 12 V DC
– Current consumption
max. 9 mA at 230 V AC
max. 170 mA at 12 V DC
– Power loss (of power supply unit)
max. 1.15 W at 230 V AC
(at efficiency level 60 %)
max. 0.35 W at 12 V DC
(at efficiency level 82 %)
– Signalling contacts
6 A / 250 V AC
Connections:
– EIB / KNX
Bus connection terminal,
0.6 to 0.8 mm Ø, single-core
– Mains voltage, auxiliary voltage,
Screw terminal
signalling
contact
0.2...2.5
mm
2
finely stranded
0.2...4
mm
2
single-core
– Tightening torque
max. 0.6 Nm
– Telephone connection
– Terminals
0.2....2.5 mm
2
finely stranded
0.2...4
mm
2
single-core
– Tightening torque
max. 0.6 Nm
– plug-in
RJ 11 socket
– LAN connection
RJ 45 socket for 10 Mbit networks,
10 Base-T IEEE 802.3
Operating and
display elements:
– ON LED, green
Displays that device is ready
for
operation
– FAULT LED, red
Displays an internal device fault
–
✆
LED, yellow
Displays that the device is dialling
(flashes) / occupied telephone line
– LAN/LINK LED, yellow
Displays the connection to a
network (link) and
telegram traffic (flashes)
– LED above bus connection,
red with push button
For assigning the physical address
Type of protection:
– IP 20
In accordance with DIN EN 60529
Protection class:
– II
In accordance with DIN EN 61140
Insulation category:
– Overvoltage category
III in accordance with
DIN EN 60664-1
– Pollution degree
2 in accordance with
DIN EN 60664-1
EIB / KNX
safety extra-low voltage:
– SELV 24 V DC
Temperature range:
–
Operation
–
–
0 ° C ....+ 45 ° C
– Storage
– 5 ° C ....+ 55 ° C
– Transport
– 5 ° C ....+ 70 ° C