TLE Series 625 to 1000 PurePulse™ UL S2
UPS Installation Guide / REV-B
TLE Series 625 & 750 - Installation notices in case of power connection with Dual Input Utility
Fig. 4.9.2-3 625 & 750 - Interconnection links BR1, BR2 and BR3
For Dual Input Utility, Bypass and Rectifier, the interconnection links BR1, BR2 and BR3 must be
removed (see Fig. 4.9.2-3).
BR3
BR2
BR1
BR3
BR2
BR1
L2-2
L3-2
N
Utility Neutral
Load Neutral
L2-1
L3-1
L1-2
L1-1
Load
L3
Load
L2
Load
L1
Interconnections links
BR1, BR2 and BR3
must be removed!
!
N
Utility Neutral
Load Neutral
1
Rectifier
Utility
2
Bypass
Utility
Q1
TLES_
UL_62
5-750
_S2_U
PS BR
1-2-3_A
BB_01
US