TLE Series 625 to 1000 PurePulse™ UL S2
UPS Installation Guide / REV-B
4.9.6
Use of TLE Series 625 to 1000 as Frequency Converter
Note!
The UPS needs the connection of the Neutral at the input Bus Bars.
Permanently running the UPS without Bypass supply requires a change of internal wiring to be
performed by an ABB Service Technician only.
When the TLE Series 625 to 1000 is utilized for
different
output frequency compared to the input frequency
, the
Automatic Bypass is disabled, therefore the Load cannot be transferred to Utility in case of overload, short
circuit, or inverter failure.
In situations where the UPS needs to be powered down for maintenance purposes, the critical Load must also be
powered down during this time.
When the set-up parameters of the UPS are set for frequency converter, the
eBoost™ Operation Mode
is
automatically disabled.
Fig. 4.9.6-1 TLE Series 625 to 1000 - Interconnection links BR1, BR2 and BR3
In order to avoid improper operation, only the Rectifier input should be powered (
L1-1, L2-1
and
L3-1
/ Fig. 4.9.2-
1 & 4.9.4.1), therefore the interconnection links
BR1, BR2
and
BR3
, on the input bus bars,
must be removed
.
See pictures above and Fig. 4.9.6-1.
Special care must be taken in choosing the
fuse ratings
installed in the output distribution
(max. 20% of the
UPS rated current)
.
Avoid high inrush current due to transformer magnetization or motor starting.
Note!
Only an ABB Service Technician may change a unit from Frequency Converter into a normal UPS
(with Bypass) or a normal UPS to a Frequency Converter (with Bypass).
TLE Series 625 & 750
TLE Series 1000
BR3
BR2
BR1
BR3
BR2
BR1
L2-2
L3-2
N
Utility Neutral
Load Neutral
L2-1
L3-1
L1-2
L1-1
Load
L3
Load
L2
Load
L1
Interconnections links
BR1, BR2 and BR3
must be removed!
!
N
Utility Neutral
Load Neutral
1
Rectifier
Utility
2
Bypass
Utility
Q1
Q1
TLES
_UL_
625-1000_
S2_UP
S BR1-2
-3_AB
B_01U
S