B0431
Emax X1-Tmax T7-Tmax T8
38/66
Doc N°
Mod.
Apparatus
Scale
Page No
1SDH000587R0002
Current
protections
PR332/P
PR333/P
Disabling
Disabling of TRIP only
Zone selectivity
Start-up thr
eshold
Thermal memory
Trip Threshold
Trip time
Trip
threshold
tolerance
(2)
Trip time
tolerance
(2)
G
(4) (6)
(t=k/I
2
)
0,1xIn
≤
I
4
≤
1xIn
step 0,02xIn
0,2xIn
≤
I
4 Start-Up
≤
1x I
4
0,1s
≤
t
4
≤
1s, step 0,05s
(minimum trip time)
@I
f
>4In
±7%
±15%
Gext
(6)
(t=k)
0,1xIn
≤
I
4
≤
1xIn
step 0,02xIn
@I
f
>I
4
0,1s
≤
t
4
≤
1s, step 0,05 s
0,1s
≤
t
4 start-up
≤
30s, step
0,02s
0,04s
≤
t
4 sel
≤
0,2s, step 0,01s
±7%
The best of the
two data±10%
or 40ms
Gext
(6)
(t=k/I
2
)
0,1xIn
≤
I
4
≤
1xIn
step 0,02xIn
0,1s
≤
t
4
≤
1s, step 0,05s
(minimum trip time)
@I
f
>4In
±7%
±15%
Rc (Idn)
Idn =3-5-7-10-20-
30A
0,06-0,1-0,2-0,3-0,4-0,5-
0,8s
(3)
-20%
÷
0
0,06s
(5)
U
(t=k)
2%
≤
I
6
≤
90%
step 1%
0,5s
≤
t
6
≤
60s, step 0,5s
±10%
The best of the
two data±10%
or 40ms
OT
(temp=k)
Fixed, defined by
ABB
Instantaneous
± 5°C
Iinst
Automatic, defined
by ABB
Instantaneous
UV
(t=k)
0,5xUn
≤
U
8
≤
0,95xUn
step 0,01xUn
0,1 s
≤
t
8
≤
5 s, step 0,1 s
± 5%
The best of the
two data±10%
or 40ms
OV
(t=k)
1,05xUn
≤
U
9
≤
1,2xUn
step 0,01xUn
0,1 s
≤
t
9
≤
5 s, step 0,1 s
± 5%
The best of the
two data±10%
or 40ms
RV
(t=k)
0,1xUn
≤
U
10
≤
0,4xUn
step 0,05 Un
0,5 s
≤
t
10
≤
30 s, step 0,5 s
± 5%
The best of the
two data±10%
or 40ms
RP
(t=k)
- 0,3xPn
≤
P
11
≤
-0,1xPn
step 0,02 Pn
0,5 s
≤
t
11
≤
25 s, step 0,1 s
± 5%
The best of the
two data± 10%
o 40 ms
UF
0,9fn
≤
f
12
≤
0,99fn
step 0,01 fn
0,5 s
≤
t
12
≤
3 s, step 0,1 s
± 5%
The best of the
two data±10%
or 40ms
OF
1,01fn
≤
f
13
≤
1,1fn
step 0,01 fn
0,5 s
≤
t
13
≤
3 s, step 0,1 s
± 5%
The best of the
two data±10%
or 40ms
LC1/LC2
load Control
50%
÷
100% step
1%xI
1
Warning Iw
0,3
÷
10I
n
step 0,05xI
n
± 10%
10
÷
40 ms
MM
(7)
(t=k)
1,5xIn
≤
I
5
≤
4xIn
step 0,1xIn
≤
30 ms
@ I
f
>I
5
±10%
(1)
The minimum value of this trip is 1s regardless of the type of curve set
(self-protection).
(2)
These tolerances are based on the following assumptions:
- energized protection release in service conditions (without start-up) with
2 or 3 phases energized and/or in the presence of auxiliary supply.
- Preset trip time
≥
100 ms.
-
Temperatura e correnti entro i limiti di funzionamento.
(3)
The interval of time for which the protection is activated can be selected
via Ekip Connect, and is calculated from the moment the CB closes.
(4)
Protection G can be automatically disabled by the release on the basis of
the current measured. Per le casistiche 1.6.8.
(5)
Max trip time.
(6)
La soglia minima delle protezioni G e Gext, in assenza di Vaux diventa
0,2In.
(7)
Available with PR332/P MM.
For all cases not covered by the above hypotheses, the following tolerance
values apply:
Protection
Trip threshold
Trip time
L
Release between
1,05 e 1,25 x I1
± 20%
S
± 10%
± 20%
I
± 15%
≤
60ms
G
± 10%
± 20%
Others
± 20%
B1751