4.7. BT030-USB
Using BT030-USB, the protection release can communicate with a PC in the wireless mode or via USB,
thereby adding to the range of information available to the user.
Communication is enabled via Ekip Connect SW, the installation package of which is in the BT030-USB set.
This set also includes the USB cable and batteries for use in the wireless configuration.
The unit is connected to the protection release by means of the front service connector.
4.8. EKIP T&P
Ekip T&P allows protection release energizing, communication and testing via a PC by means of a USB adapter.
Similarly to BT030-USB, communication is enabled via Ekip Connect SW, the installation package of which is in the Ekip T&P set.
The set includes the USB module and a series of adapters for various types of protection releases.
WARNING: Ekip T&P must only be used with the dedicated cable, compatible with PR33x/P protection releases
(the picture below is for explanatory purposes only). Consult the Ekip Connect SW Operation Manual
(1SDH000891R0001) for further details.
4.9. HMI030
Protection releases PR33x/P can be connected to the front external unit of HMI030 switchgear so
as to display the current values measured.
HMI030 connects to the connector on the rear side, on the protection release, the external con-
nection of which is provided by the contacts on the terminal box in the CB.
Auxiliary power supply for the protection release and HMI030 is required for this function.
HMI030 power supply
Auxiliary power supply
24 V DC +/-20%
Maximum ripple
5%
Rated power @ 24 V
1,2W
Consult the Operation Manual of the unit (1SDH000573R0001) for further details.
4.10. Flex interface
Flex interfaces are electronic units that can be installed on DIN rail, with analog and/or digital inputs
and outputs, which can be connected to the protection release via Local Bus Local.
The Flex Interface family comprises module MM030 (connected on one side to the Local Bus of the
protection release and on the other side to all the modules installed) and the modules of the AD series.
If connected to MM030, the HMI030 module is also part of the Flex Interface family.
All the configurations and connection solutions are described in the dedicated operation manuals (as
shown in the attached table).
Auxiliary power supply for the protection release and Flex Interface is required for this function.