Operation Manual / TPS48-D/E.. - TPS61-D/E..
3 Commissioning / 3.1 Oil supply
© Copyright 2020 . All rights reserved.
HZTL2410_EN
Rev.F
March 2020
Lubricating oil temperature at the inlet
CAUTION
Machine damage
Machine damage may result if the oil temperature at the oil inlet ex-
ceeds the permissible range.
u
Keep the oil temperature at the oil inlet as specified in the following
table.
Status for operation
Oil temperature at the in-
let
T
oil,inlet
Admissible
30 … 105 °C
Temporarily admissible (< 1 h)
→
alarm
> 105 °C
Not admissible
→
stop engine
> 110 °C
Not admissible
→
do not start engine (before
starting: preheat oil)
< 30 °C
Lubricating oil temperature at the outlet
The oil temperature at the outlet depends mainly on:
¡
lubricating oil temperature and pressure at the oil inlet
¡
engine load and turbocharger speed
¡
exhaust gas temperature
The maximum permissible oil temperature at the outlet is listed in the
following table. The specified oil outlet temperature must be regarded
as an alarm value for turbocharger operation and be monitored in ac-
cordance with standard regulations.
Status for operation
Oil temperature at outlet
T
oil,outlet
Admissible
≤
160 °C
Temporarily admissible
→
alarm
> 160 °C
Not admissible
→
stop engine
> 180 °C
Admissible
≤
T
oil,inlet
+ 55 K
Temporarily admissible
→
alarm
> T
oil,inlet
+ 55 K
If the turbocharger has been operated outside the permissible range for
a prolonged period of time, ABB Turbocharging recommends having the
turbocharger inspected by an ABB Turbocharging Service Station.