Installation Guide
TruFit
®
Power Distribution Unit
│
94-1100-00002873 A0 EN 25/34
•
Neutral & Ground bus terminals
Terminals are provided for Panelboard neutral and ground connections, as shown below.
Recommended Torque values:
Wire AWG
Torque lb-in.
14-10 Cu, 12-10
AL
20
8
25
6-4
35
two 14 or 12 Cu,
two 12 or 10 AL
25