22
TTH200
HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH200-EN REV. B
… 9 Commissioning
… Parameterization of the device
Parameter descriptions
DTM menu path, parameters
Description
<Device> / <Extras>
<Write Protection>
Activates write protection for the entire device
• Yes: locked, entry combination:
≠
0110
• No: unlocked, entry combination: 0110
<Device reset>
Configuration data is reset to factory settings
(see
Factory settings
on page 24).
<Factory reset>
Configuration data is reset to factory settings
(see
Factory settings
on page 24).
In addition, the adjustment data and DAC adjustment values are also reset to factory settings.
• Yes / OK
<Device> / <Configuration>
<Sensor / Sensor type>
Selects sensor type:
• Pt100
(IEC751)
• Pt1000
(IEC751)
• Thermocouple type K (IEC584)
• Thermocouple type B (IEC584)
• Thermocouple type C (ASTME988)
• Thermocouple type D (ASTME988)
• Thermocouple type E (IEC584)
• Thermocouple type J (IEC584)
• Thermocouple type N (IEC584)
• Thermocouple type R (IEC584)
• Thermocouple type S (IEC584)
• Thermocouple type T (IEC584)
• Thermocouple type L (DIN43710)
• Thermocouple type U (DIN43710)
• Thermal voltage -125 to 125 mV
• Thermal voltage -125 to 1100 mV
• Resistance 0 to 500
Ω
• Resistance 0 to 5000
Ω
• Pt10
(IEC751)
• Pt50
(IEC751)
• Pt200
(IEC751)
• Pt500
(IEC751)
• Pt10
(JIS1604)
• Pt50
(JIS1604)
• Pt100
(JIS1604)
• Pt200
(JIS1604)
• Pt10
(IMIL24388)
• Pt50
(IMIL24388)
• Pt100
(MIL24388)
• Pt200
(MIL24388)
• Pt1000
(MIL24388)
• Ni50
(DIN43760)
• Ni100
(DIN43760)
• Ni120
(DIN43760)
• Ni1000
(DIN43760)
• Cu10 (OIML R 84), a=4270
• Cu100 (OIML R 84), a=4270
<Sensor / Connection>
Sensor connection type relevant for all Pt, Ni, Cu resistance thermometers
• Two-wire: sensor connection type in two-wire technology
• Three-wire: sensor connection type in three-wire technology
• Four-wire: sensor connection type in four-wire technology
<Sensor / Line resistance>
Sensor line resistance relevant for all Pt, Ni, Cu resistance thermometers with a two-wire circuit
Value range: 0 to 100
Ω