Electrical
connection
OI/TTR200-EN TTR200
17
Standard application with HART functionality
Field Control
room
Fig. 6
A Transmitter
B Power supply / SPS input with supply
Adding resistance R
250
increases the minimum supply voltage:
U
Mmin
≤
U
Smin
+ 0.02A x (R
Ltg
+ R
250
)
Where
U
Mmin
: Minimum operating voltage of transmitter (refer to technical data for transmitter)
U
Smin
: Minimum supply voltage of repeater power supply / SPS input
R
Ltg
:
Line resistance between transmitter and power supply
R
250
:
Resistance for HART functionality