background image

 

TZID-C

  

 

 

 

 

QUICK-START

 

Valve Positioner 

 
Brief Operating Instructions for TZID-C  
 

Commissioning 

1. Turn on the air supply to the positioner.  Check all tubing and remedy any leaks. 
2. Apply the 4...20 mA analog input signal to the positioner, obs & - polarity. 
3. Check for proper mounting: refer to instruction manual if needed. 

  Open front dust cover from positioner to access the local control keys. 

  Press and hold 

MODE

  Additionally briefly press 

until mode 

1.3 MAN_SENS 

is displayed. 

 Release 

MODE

 Press 

 to move the actuator to its mechanical limit stops in both directions, and note the 

values. 

  The angle of rotation on the display is indicated in degrees. Recommended positions of limit stops: 

¾

  > -28° and < +28° for linear actuators 

¾

  > -57° and < +57° for rotary actuators 

  Adjust the mounting position of the positioner in relation to the actuator if required. 

4.  Select the appropriate Configuration procedure below and continue with 

Step 5

… 

 

Configuration With Software Rev 2.XX and higher 

(see other side for Software Rev 1.1 and lower) 

 

5. 

Run the standard autoadjustment function using either the linear or rotary procedure as follows: 

Note:  the actuator moves during autoadjust; take necessary precautions & take valve out of service. 
 

For linear actuators:

1

- Press and hold 

MODE 

until 

ADJ_LIN 

is displayed, then release. 

- Press 

MODE 

again and hold it down until the 

3

 to 

countdown finishes. 

- Then release 

MODE

Standard autoadjustment starts. 
 

For rotary actuators:

1

- Press and hold 

ENTER 

until 

ADJ_ROT 

is displayed, then release. 

- Press 

ENTER 

again and hold it down until the 

3

 to 

countdown finishes. 

- Then release 

ENTER

Standard autoadjustment is started. 
 
When the autoadjustment function is finished 

successfully

, the parameter settings are 

automatically 

saved 

and the positioner returns to Control Fixed, operating mode 1.1.  To change operating mode, see Selecting the 
Operating Mode section on next page. 
 
If standard autoadjustment should fail, the procedure is automatically interrupted, and an error code is indicated. 
In this case press and hold 

 for approx. 3 seconds. The positioner returns to mode 

1.3 

MAN_SENS 

(manual adjustment within sensor range). Check the assembly for proper mounting and, if required, readjust it. 
Repeat the standard autoadjustment function. 
 
6. 

If required: Adjust the dead band and tolerance band 

This step is only necessary for critical actuators, e.g. very small ones. Usually, it can be skipped. 
 
 