5.5 Connection to the Oil Conservator
NOTE:
If oil filling is carried out under vacuum without oil conservator, this section
is carried out after the oil filling.
Remove the transport cover on the flange for connection to the oil conservator. Make
sure the O-ring is in place on the flange and connect the pipe to the oil conservator.
Tighten the nuts.
CAUTION
In case where the conservator is common for the transformer and the on-load tap-
changer, an oil filter must be placed in the pipe between the on-load tap-changer and
the conservator.
Oil filter with housing can be ordered from ABB.
5 Final Assembly
60