11
10. Technical
details
– Direction of operation:
clockwise to close easily changeable, see point 5.h.
– Motor: Rectifi ed DC, permanent magnet type
Rated voltage
Normal control current
Max. current
Recommended
U/V
In/A
Imax/A
M.c.b.
24 VDC
12
40
- S202 K8
48 VDC
6
20
- S202 K4
60 VDC
5
17
- S202 K4
110 VDC
2
5.5
- S202 K2
125 VDC
2
5.5
- S202 K2
220 VDC
1
3
- S282 UCK 1
230 VAC
1
3
- S202 K1
– Manual operating device with operating handle
UEKO-ZK
1
– Terminal block 6 mm
2
– Anti-condensation heater 5 W
(to be ordered separately)
– Operating time at standard load 5...8 s
Operating time at different load
1) With accessory: Coupling ring UEMZ 452
UEMC 40 UEMC 40 UEMC 40
A1
A2 B1 B2
D1 D2
Torque
Nm
200 200 300 300
200 200
Weight kg
14.5
14.5
12.5
12.5
13
13
Contactors:
Closing power
W
3
3
3
3
3
3
Holding power
W
3
3
3
3
3
3
Shortest control pulse
s
0.1
0.1
0.1
0.1
0.1
0.1
Operating angle
Degr.
190
190
110
110
150
150
Degr.
210
1)
210
1)
Summary of Contents for UEMC 40 A Series