Motor Management Parameters Continued
Para-
meter
Number
Parameter
Description, Explanations
Options
Adjustable
via
15
Emergency
Start
To allow start-ups even if the
thermal overload protection
would prevent them.
Off (0), On (1)
All
14
Fault auto
reset
Automatically reset of se-
lected protection faults (PTC,
overload (EOL), imbalance
and phase loss).
Faults triggered from the
UMC100 multifunction inputs
and the IO module are not
automatically reset. There are
separate parameters.
Off (0), On (1)
All
81
Custom app
parameter
Allows to specify a value
which is available in the cus-
tom application.
0 ... 255
All
Limit the Number of Starts
148
Num Starts
Allowed
Defines the number of
permissible starts in the time
window.
0 ... 32
Zero switchs off the start limit
function.
All exclu-
ding GSD-
PDQ22
149
Num Starts
Window
Defines a time window in
which only a certain number
of starts are allowed.
0min ... 255min (4,25h) in steps of
1min
Default value: 0
All exclu-
ding GSD-
PDQ22
150
Num Starts
Pause
After the motor was stopped
a new start is not possible
before the pause time is
over.. This paramter can be
used independantly of the
other parameters i.e. without
limiting the number of starts
in a time window.
0min ... 255min (4,25h) in steps of
1min
Default value: 0
All exclu-
ding GSD-
PDQ22
155
Num Starts
Overrun
Reaction if no start is left
anymore but a start com-
mand was issued.
0: Disabled
1: Trip
2: Warning
All exclu-
ding GSD-
PDQ22
221
Num Starts
Prewarn
Reaction if only one start is
left.
0: Disabled
1: Trip
2: Warning
All exclu-
ding GSD-
PDQ22