- 128 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
143
Voltage Dip
Duration
Max. voltage dip duration time
before a trip is signalled.
0.1...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 1...255
Example: 5 means 0.5s
All exclu-
ding
GSD-
PDQ22
144
Autorestart
Window
If the voltage dip ends within
this time window an autorestart
is triggered (if enabled).
0.1 ... 1s in steps of 0.1s
Unscaled: 1...10
Example: 5 means 0.5s
UMC100-
PAN
PBDTM
145
Autorestart
Delay
Delay until the motor is restar-
ted
0 ... 255s
UMC100-
PAN
PBDTM
147
Enable Au-
torestart
Enables the autorestart of the
motor after end of the voltage
dip
Off (0)
On (1)
UMC100-
PAN
PBDTM
156
Dip Restart
Level
Voltage level indicating the end
of the low voltage situation
50 ... 115% of U
e
in steps of 1%
Default value: 90
157
Dip Level
Voltage level indicating a low
voltage situation and triggering
the DIP logic.
50 ... 115% of U
e
in steps of 1%
Default value: 70
Internal Ground Fault
10
Earth Flt Trip
Level
Above this ground fault current
a ground fault tip is triggered.
A value of 255 % disables the
trip.
20 ... 80 in % of nominal current
I
e1,2
(255 = off)
Example
:
Ie = 100A, Earth Flt Trip Level = 35%.
Then a earth fault current of 35A
triggers a trip.
All
11
Earth Flt Trip
Delay
Delay time until a ground fault
trip is triggered.
0...25.5s in steps of 0.1s
Default: 0,5s
Unscaled: 0...255
Example: 20 means 2s
All
12
Earth Flt
Warn Level
Above this ground fault cur-
rent a ground fault warning is
triggered.
A value of 255% disables the
warning.
20 ... 80 in % of nominal current
I
e1,2
(255 = off)
All ex-
cluding
GSD
PDQ22
13
Earth Flt
Warn Delay
Delay time until a ground fault
warning is triggered.
0...25.5s in steps of 0.1s
Default: 0,5s
Unscaled: 0...255
Example: 20 means 2s
All ex-
cluding
GSD
PDQ22
16
Earth Flt
Detection
Defines when the internal
ground fault protection function
is active.
0: Always
1: After Startup
All
Protection Parameters Continued