Power Scale
Factor
Factor that can be used
to scale the active and
apparent power so that
the r
esulting value fits in a
WORD. This is needed for
bus transfer.
0 = 1
1 = 10
2 = 100
3 = 1000
Example:
U
e
is 400V, I
e
is
200A, Rated PF is 0,8.
The nominal active power is then
400*200*1,73*0,8 = 110720.
To transfer this value via fieldbus
it must be scaled e.g. by 10. So
the resulting value is 110720/10
= 11072 which fits in a WORD.
All excluding
GSD-PDQ22
219
THD Warning
Level
Above this level of Total Har-
monic Distortions a warning
is triggered
3 ... 10% in steps of 1%
10 disables the function
All excluding
GSD-PDQ22
222
THD Warning
Delay
Delay time until an warning is
triggered
0 ... 255 s in steps of 1s
Default is 5s
All excluding
GSD-PDQ22
220
Load Startup
Delay
Delay time until load (e.g.
pump) has started up and
power supervision functions
should become active.
0 ... 255 s in steps of 1s
All excluding
GSD-PDQ22