- 33 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
3 Commissioning
This chapter provides an overview of the required commissioning steps. For details about the single steps
please consult the related chapters.
Commissioning Steps
To commission the UMC100-FBP, proceed as follows:
A) Wiring
Wiring and 24 V DC / 0 V connection:
Hard wire with switch apparatus and other components acc. to the application requirements.
Connection of contactors: Use spark suppression, for larger contactors also interface relays to maintain a
good service life of the UMC100 internal relays.
Motor wiring: Check the wiring of the motor to ensure correct setting of Ie for perfect motor protection.
When using UMC100 with motors of nominal currents < 1 A please read section "Operation Details for
Motors with Small Set Currents". If the nominal motor current is above 63 A read section "Connecting
External Current Transformers (CTs)" on how to use the UMC100 with external current transformers.
If an IO expansion module is used connect the UMC100 with the IO module and hard wire the inputs of
the expansion module acc. to the application requirements.
B) Switching on the power supply
Switch on the supply voltage of the UMC100. If connected with a FieldBusPlug also ensure that the
FieldBusPlug is powered. In the fault-free state, the green UMC100 LEDs should light up.
LEDs on the UMC100:
Green (ready)
On
Yellow (motor running) Off
Red (fault/trip)
Off
LEDs on the FieldBusPlug:
In fault free state H1/H3 (left upper and lower LEDs) should light up. If no cyclic bus master is
active H2 (upper right LED) is flashing. See the technical description of the FieldBusPlug in use.
Continue with Step C) if fieldbus communication is required or continue with step D) to start the configuration.
In case of an error use the LED/UMC100-PAN information of the UMC100/FieldBusPlug to find out the
cause of the fault (see section
"Fault Handling").
C) Setting the fieldbus node address
Before connecting the UMC100 to a fieldbus network (e.g. PROFIBUS) set the fieldbus address using
UMC100-PAN. That means the slave address is directly adjusted and stored in the UMC100.
To change the bus address, press
Menu
, select
Communication
and then
Bus Address
.
Adjust the address within the limits defined by the fieldbus type (for PROFIBUS e.g. 2 to 125).
D) Start configuring the UMC100 via LCD panel, laptop or control system
The following parameters need to be adjusted
•
Motor management related parameters e.g. the control function
(see section "Configuring the Motor Management Functions")
•
Parameters defining how to start and stop the motor from the different control places
(see section "Configuring the Motor Management Functions -> Starting and Stopping the Motor").
•
Parameters related to the motor and its protection functions
(see section "Configuring the Motor Protection Functions").
•
Parameters related to the fieldbus communication interface
(see section " Configuring the Fieldbus Communication")
•
Other settings such as the panel language or the usage of a connected DX1xx module.