- 148 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 8.2.2~3
Par.
No.
Menu
No.
Menu point name
Display:
7-segm.
Default
Range
Description / remark
take over
-
2.7
Self Test
(4.3.4)
Internal hardware and software test
-
2.7.1
Start with [ENTER]
2.7.2
Shows the correct test run. Test is ok if
no fault signal is set after the test.
17
2.8
Reverse lock-out
time
(4.3.4)
Only for bidirectional starter!
Time starts running with the OFF com-
mand. An Off command is nessesary
between run forward and reverse, that
means between RUN FORWARD and
RUN REVERSE command.
A RUN command into the other di-
rection will be only acepted when the
Reverse lock-out time has elapsed.
(adjusting 0 results in 0.2)
during
motor off
2.8.1
show / change
2 s
0.2-3600 s
Show and change Reverse lock-out
time in steps of 1 s
16
2.9
Star-delta
starting time
Only for Star-delta starter!
Starts with the RUN command.
during
motor off
Run-time limit
(4.3.4)
Only for Actuator 1-4!
This time is used to survey the running
time from Closed to Open position and
vice versa
(see parameter
Start surveying time /
Star-delta changeover mode
).
2.9.1
show / change
60 s
0-3600 s
Show and change time in steps of 1s
10
2.10
Cooling time
(4.3.4)
Cooling time simulates the cooling
behaviour of the inoperating motor
after tripping.
Remark:
During Cooling time is running, RUN
commands are not accepted.
WARNING is monitored.
during
motor off
2.10.1
show / change
120s
30 - 3600s
Show and change Cooling time in
steps of 1s
18
2.11
Operating hours
(4.3.4)
All hours are counted but the unit
place is not displayed in the Control
Panel (10 hour steps). Displayed fi gu-
res 00.00 - 65.53 correspond with real
00‘000 to 65‘530
during
motor off
2.11.1
show / change
0
0 - 65‘535