- 15 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
3.2 Wiring
3.2.1 Wiring with switch apparatus
Hard-wire with switch apparatus and other components referring the application requirements.
Wiring examples see below and chapter 7.
Example: Direct starter
Fig. 3-1: UMC22-FBP as Direct starter (example)
Chapter 3.2.1~1
24 V
0 V
690 / 400 V
UMC22
11
24
V
24
V
12
13
14
15
DI
2
16
17
18
DI
4
DI
5
DI
0
DI
1
DI
3
0 V 24 V
10
0
V
DI1 DI2 DI3 DI4 DI5
230 V DO1
DO
C
5
T1
T2
6
DO
C
DO
0
7
DO
2
9
DO
1
8
DO2
T1 T2
N
max.
200 mA
24 V
K1
K1
external
supply
supply
inputs
2CDC 342 009 F0207
free inputs,
signals directly to the fieldbus
With parameter Check-back = 1 (Auxiliary contacts):
the digital input DI0 is used to survey the contactor
(default: 2 (Motor current))
With parameter Control function = 3 (Direct starter):
the relay output DO0 is used to coltrol the motor contactor
free outputs,
commands direct from fieldbus
Short circuit
protection device
PTC inputs
Summary of Contents for UMC22-FBP
Page 167: ......