Universal Motor Controller UMC22-FBP
Software version 4.0
Par.
No.
Menu
No.
Menu point name
Display:
7-segm.
Default
Range
Description / remark
take over
21
3.7
DI2 Multi-function
input
(4.3.4)
01...49
Multi-function input DI2 offers additi-
onal possibilities to survey the motor
and the production process it is used
for.
Remarks:
Multi-function input DI2 replaces -
keeping the compatibility - the former
parameter Fault input (DI2).
The same functions are available for
DI0 and DI1 but can be parameterized
only via bus master / fi eldbus.
during
motor off
3.7.00
Transparent
P.000
Input status is monitored only to the
fi eldbus.
(correspondes to former parameter
Fault input DI2 = Off)
3.7.01
Fault signal always
/ undelayed
If the input DI2 = 0 the internal fault
signal is set immmediately.
In the following:
Relays outputs open, motor is stop-
ped
fault is monitored to the fi eldbus
If parameter
Fault output = On
out-
put DO2 is set to 1.
The fault can be only acknowledged
when the input gets high signal. After
successful acknowledge the motor
can be restarted.
(correspondes to former paremeter
Fault input DI2 = On)
3.7.02
Motor off always /
undelayed
If one of the inputs DI0, DI1 or DI2 = 0
the motor is stoped immediately. The
internal fault signal ist not (!) set.
Chapter 8.2.3~6