- 161 -
UMC22-FBP
FieldBusPlug / Issue: 02.2008
V 6
Universal Motor Controller UMC22-FBP
Software version 4.0
Par.
No.
Menu
No.
Menu point name
Display:
7-segm.
Default
Range
Description / remark
take over
-
3.11
Bus connection
(4.3.4)
Not a parameter, only for stand alone
operation without fi eldbus. Allows to
use the UMC22 without FieldBusPlug,
e.g. as Overload relay.
continued
power up
transition
-
3.11.0
Stand alone
Stand alone operation without fi eld-
bus, controlled by digital inputs and
Control Panel
power up
transition
3.11.1
Connected to the
fi eldbus
On
Operation with fi eldbus
-
3.12
Bus fault reaction
(4.3.4)
All cases when UMC22 does not
receive valid telegrams, either when
the control system or the fi eldbus or
the FieldBusPlug is out of order or
interrupted.
during
motor off
3.12.1
Relays off
Relays
off
Relay outputs of UMC22 will be swit-
ched off if a bus fault occurs.
3.12.2
Relays retain
status
Relay outputs of UMC22 retain their
status if a bus fault occurs.
-
3.13
Parameter lock
(4.3.4)
Locks writing all parameters via con-
trol system / fi eldbus and via Control
Panel
immedia-
tely
3.13.1
Parameter enabled
Off
Writing parameters enabled
3.13.2
Parameter locked
Writing parameters locked
Summary of Contents for UMC22-FBP
Page 167: ......