- 28 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
NEW
3.4.4 Inching mode
The inching mode (jogging) can be used to start a motor via the digital inputs and keep it running as long
as the inputs are active. The inching mode is not possible from the LCD panel. A present stop command
(from the fi eldbus or another source) is dominant and inhibits the start of the motor or stops an already
running motor.
L006 and L008:
The stop input must be connected to 24VDC if unused.
Fwd or
Rev signal
DI3/DI4
Relais
Output
UMC
Stop signal by
bus or panel
Stop signal
DI5
2CDC342034F0207
L007 and L009:
The stop input must be connected to ground or left open if unused.
Fwd or
Rev signal
DI3/DI4
Relais
Output
UMC
Stop signal by
bus or panel
Stop signal
DI5
2CDC342035F0207
Fig 3-8-1: Inching mode. Please note that an edge is required to start the motor.
For more details see section
4.3.
Chapter 3.4.4~1
Summary of Contents for UMC22-FBP
Page 167: ......