UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.4~1
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Contr
ol
system
(digital
value if
dif
fer
ent)
Contr
ol
Panel
Address
Accessible only via Control Panel (menu point: Addr) or Addressing Set CAS21-FBP!
Enter slave address.
-
*
Entering "999" results in "A---" = no valid address
* Range depends on the fi eldbus type
Address check
26
Accessible only via control system!
Details see chapter 3.3.2.
Off
(0)
-
Address check off (= default)
:
UMC22 address is valid on fi eldbus.
On
(1)
-
Address check activated:
If the UMC22 and the FieldBusPlug contain different addresses the user
must decide.
Automatic
fault reset
11
Accessible via control system or Control Panel (menu point: A.rES)!
Only for control function
Overload relay
due to safety considerations.
Disabled
(0)
AroF
Automatic fault reset off (= default):
Acknowledge via Control Panel or fi eldbus necessary to reset fault. To
switch on again, cooling time must be elapsed.
Autoreset
(1)
Aron
Automatic fault reset activated
:
Automatic reset of fault when fault condition is off and cooling time has
elapsed. Fault is not monitored.
Blocking
current
threshold
23
Accessible only via control system!
0-795 %
(0-159)
-
Blocking protection aktivated:
0-795 % x Set current (step: 5 %): 795 % = 5 % x 159
Fault signal when start-up time has elapsed and then current is above
threshold for > 1 s.
Remark:
Blocking sets the internal fault signal and the monitoring telegram bit
OVERLOAD and displays trip on the Control Panel. The cooling time is not
started.
800 %
(160)
-
Blocking protection off (= default):
800 % x Set current (step: 5 %): 800 % = 5 % x 160
Blocking protection is inactive.
4.3.4 Parameter - Details in alphabetical order