- 90 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.0008
V 6
7.3.3 Interface and data overview
Hardware Inputs / Outputs
Terminal
13
14
15
16
17
18
Device input
(to bus)
DI0
1)
(Multi-function
input or
check-back)
DI1
1)
(Multi-function
input)
DI2
1)
(Multi-function
input)
DI3
DI4
1)
(Local: On)
DI5
1)
(Local: Off)
Terminal
7
8
9
Device output
(from bus)
DO0
Forward
DO1
DO2
1)
(Fault output)
Chapter 7.3.3~1 Direct starter
Monitoring telegram, digital
Bit No.
7
6
5
4
3
2
1
0
Byte 0
WARNING
FAULT
LOCAL
CONTROL
-
-
RUN
FORWARD
OFF
-
Byte 1
DI5
1)
(UMCinput)
DI4
1)
(UMCinput)
DI3
1)
(UMCinput)
DI2
1)
(UMCinput)
DI1
1)
(UMCinput)
DI0
1)
(UMCinput)
-
-
Monitoring telegram, analog
Byte 0 and Byte 1: Motorcurrent in % of set current
Command telegram, digital only
Bit No.
7
6
5
4
3
2
1
0
Byte 0
-
FAULT
RESET
)
AUTO
MODE
PREPARE
EMERGENCY
START
SELF
TEST
RUN
FORWARD
OFF
-
Byte 1
DO2
1)
(UMC output)
DO1
(UMC output)
-
-
-
-
-
Diagnosis telegram
Bit No.
7
6
5
4
3
2
1
0
Fault
Byte 0
-
Self test failed
F010
2)
Fault signal
on DI0, DI1
or DI2
1)
F011
2)
-
-
-
-
-
Fault
Byte 1
Overload (trip)
fault
trip
2)
Motor blocked
F002
2)
Communi-
cation fault
F003
2)
Parameter out
of range
F004
2)
Current
check-back
fault
1)
F005
2)
-
-
Relay 0
check-back
fault
1)
F008
2)
Warning
Byte 2
Motor current
high threshold
1)
Motor current
low threshold
1)
-
Cooling time
running
°C
2)
-
Self test
running
buSy
2)
Emergency
start
prepared
-
Warning
Byte 3
If Parameter out of range: Pamameter number (leading two stages of the parameter, e.g. "02" Current factor)
If Self test fauled: Self test error number (only for service)
In all other cases:
Phase loss
trip
2
Fault on DI2
F024
2)
Faut on DI1
F023
2)
Fault on DI0
F022
2)
Earth fault
F020
2)
PTC
short-circuit
F019
2)
PTC
wire break
F018
2)
PTC
temperature
F017
2)
1)
depending on parameterization
2)
displayed on the Control Panel
Busdata details see 4.2.2.