PRIM AR Y TESTING
CURRENT S ENSORS
1VLG5000 17 C
19
4.2
Current sensors
Primary testing verifies the whole measurement chain including the sensor, cable connec-
tions and settings of the protection relay. Each current sensor has unique physical polarity.
Therefore, no polarity (physical test) is needed. The current sensor polarity can be changed
via parameter setting. Secondary winding resistance and magnetization curve tests are not
applicable either.
4.2.1
Supervision
In the protection relay, current metering is supervised by the CMMXU function. Metering ac-
curacy is stated in Table 1.
Table 1: Current metering accuracy
Characteristic
Value
Operation accuracy
•
Depending on the frequency of the
measured current: f
n
±2 Hz
•
±0.5% or ±0.002 × I
n
(at currents in
the range of 0.01...4.00 × I
n
)
A measured value under the zero-point clamping limit is forced to zero. This allows the noise
in the input signal to be ignored. Read more details in the technical manual of the protection
relay.
Table 2: Zero-clamping limits
Function
Zero-clamping limit
Three-phase current measurement (CMMXU)
1% of nominal (In)
Residual current measurement (RESCMMXU)
1% of nominal (In)
Phase sequence current meas. (CSMSQI)
1% of nominal (In)
Summary of Contents for UniGear Digital
Page 1: ...DISTRIBUTION SOLUTIONS UniGear Family UniGear Digital Commissioning and testing Guide...
Page 2: ......
Page 3: ...DISTRIBUTION SOLUTIONS UniGear Family UniGear Digital Commissioning and testing Guide...
Page 6: ......
Page 10: ......
Page 12: ......
Page 96: ......
Page 98: ...Visit us www abb com mediumvoltage Document Number 1VLG500017 Rev C...