8
1VLG5 00007 E
KEVA 24 B20
KEVA B sensor can be used in all applications up to the voltage level 24 kV. The sensor fulfils
requirements of accuracy class 0.5 for measurement purposes and accuracy class 3P for
protection purposes.
Figure 6: Voltage sensor KEVA 24 B20
Technical parameters
–
Rated primary voltage
22 /
3 kV
–
Rated power frequency withstand voltage
50 kV
–
Rated lightning impulse withstand voltage
125 kV
–
Transformation ratio
10 000: 1
–
Accuracy class
0.5 / 3P
Summary of Contents for UniGear Digital
Page 1: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Page 2: ......
Page 3: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Page 6: ......
Page 10: ......
Page 12: ......
Page 84: ...72 1VLG5 00007 E Figure94 VirtualLANs allocation in HSR PRP networks ...
Page 111: ......
Page 112: ... Visit us www abb com mediumvoltage Document Number 1VLG500007 Rev E ...