36
1VLG5 00007 E
Configuration procedure in PCM600
Only three simple steps are needed to get GOOSE engineered in PCM600.
Step 1 / 3
Creating a GOOSE data set and its entries with the IEC 61850 Configuration tool
Figure 44: Creating a new GOOSE data set and its entries
A maximum of 20 data attributes can be added to a single GOOSE data set. If a data set has
quality attributes, the attributes must be located after the status value of the same data
object.
Step 2 / 3
Configuring a GOOSE control block with the IEC 61850 Configuration tool
Figure 45: GOOSE control block properties
Summary of Contents for UniGear Digital
Page 1: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Page 2: ......
Page 3: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Page 6: ......
Page 10: ......
Page 12: ......
Page 84: ...72 1VLG5 00007 E Figure94 VirtualLANs allocation in HSR PRP networks ...
Page 111: ......
Page 112: ... Visit us www abb com mediumvoltage Document Number 1VLG500007 Rev E ...