Primary Switch Mode Inverter
UNV-F
Operation Manual
Page 19 (28)
BHB.UNV-F.D65-1050.HB101
Following diagramm shows standard values, adjustment
range and steps:
Dis-
play1
notice
Standard
Range
Step
nominal value of out-
put voltage Uo*
230
[V
AC]
200...255 0,25
[V]
monitoring threshold
of output voltage low
Uo<*
207
[V
AC]
180...230 1,0
[V]
Monitoring threshold
of output voltage high
Uo>*
253
[V
AC]
230...270 1,0
[V]
switch off threshold
input voltage high Ui>
48V:75 [V DC]
108V: 130
0...80
0...135
0,1 [V]
0,25
switch off threshold
input voltage low Ui<
48V:41 [V DC]
108V: 92
41...80
90...110
0,1 [V]
0,25
switch on again
threshold input volt-
age low Ui<
48V:45 [V DC]
108V: 96
41...80
90...110
0,1 [V]
0,25
*When adjusting thresholds Uo, Uo> with up / down keys
the moving dot shows the actual value:
For example:
Correspond to 230,0
Correspond to
230,25
Correspond to
230,5
Correspond to
230,75