Table A.1: Technical Specifications
(Continued)
Value
Property
Precision: +/-5% f.s.
Externally powered
One RS-485 serial channels configurable in MODBUS protocols
Communication ports
MODBUS speed: Selectable 9600, 19200, 38400, or 115200 baud
The serial line(s) cable(s) must not be in the same tray as the relay
contact wiring.
The relay contact(s) is (are) wired to a circuit whose voltage is higher
than 50V (AC or DC).
4 touch-buttons (UP, DOWN , LEFT, and RIGHT)
Local configuration interface
LCD display
From clean ambient air
Air source for lens cleaning
LOS (Line Of Sight) versions: 115 l/min (4 SCFM)
Air flow for lens cleaning
Excessive contaminants might require a flow up to 400l/min (14 SCFM)
FOC (Fiber Optic Cable) versions: 400 l/min (14 SCFM)
LOS (Line Of Sight) versions: 20mm H
2
O (1” W.C.) above the maximum wind
box pressure measured at the “Y” connection inlet.
Minimum cleaning air pressure
FOC (Fiber Optic Cable) versions: 400mm H
2
O (12” W.C.) above the maximum
wind box pressure measured at the “Y” connection inlet
Quartz fiber: 350°C (662°F)
Maximum fiber optic continuous
operating temperature
Glass fiber: 482°C (900°F)
1” NPT male
Mounting thread
¾ “ NPT female (N/A for connectorized versions)
Cable entry thread
Allowable cable sections:
Electrical connections (terminal
versions)
0.05÷2mm
2
for 24V
DC
Power and SHIELD (J5 terminal block)
0.08÷1.4mm
2
for all other terminal blocks
Standard yellow-green earth cable
Enclosure earth connection
4mm
2
minimum section
3m maximum length
Maximum length of electrical
connections (by function)
–
Power supply: Not specified
–
COMM (MODBUS): Depends on transmission speed
–
Analog Output (4-20mA): Not specified
8VZZ005286 B
132
A Specifications
A.1 Technical Specifications
Summary of Contents for Uvisor SF910i
Page 2: ......
Page 6: ......
Page 20: ...8VZZ005286 B 20...
Page 30: ...8VZZ005286 B 30...
Page 68: ...8VZZ005286 B 68...
Page 78: ...8VZZ005286 B 78...
Page 90: ...8VZZ005286 B 90...
Page 92: ...8VZZ005286 B 92...
Page 98: ...8VZZ005286 B 98...
Page 108: ...8VZZ005286 B 108...
Page 114: ...8VZZ005286 B 114...
Page 118: ...8VZZ005286 B 118...
Page 126: ...8VZZ005286 B 126...
Page 128: ...8VZZ005286 B 128...
Page 130: ...8VZZ005286 B 130...
Page 150: ...8VZZ005286 B 150...
Page 151: ...Appendix E Drawings 8VZZ005286 B 151 E Drawings...
Page 152: ...Figure E 1 Enclosure Quick Release Connector and Version LOS 8VZZ005286 B 152 E Drawings...
Page 153: ...Figure E 2 Enclosure NPT Cable Inlet and Version LOS 8VZZ005286 B 153 E Drawings...
Page 154: ...Figure E 3 Enclosure Quick Release Connector and Version FOC 8VZZ005286 B 154 E Drawings...
Page 155: ...Figure E 4 Enclosure NPT Cable Inlet and Version FOC 8VZZ005286 B 155 E Drawings...
Page 156: ...Figure E 5 FOC Flexible Assembly 8VZZ005286 B 156 E Drawings...
Page 157: ...Figure E 6 FOC Rigid Assembly 8VZZ005286 B 157 E Drawings...
Page 160: ...Figure E 9 Bailey Flame ON Standard Replacement 8VZZ005286 B 160 E Drawings...
Page 161: ...Figure E 10 Typical Bailey Flame ON Installation 8VZZ005286 B 161 E Drawings...
Page 162: ...8VZZ005286 B 162...
Page 170: ...8VZZ005286 B 170...
Page 178: ...G 7 Counter Flange 8VZZ005286 B 178 G Fittings G 7 Counter Flange...
Page 189: ......