D500
| CI/EDP300-EN Rev. A 21
7.2
Menu levels
There are two levels under the process display.
Process display
Information level
Operating modes menu
Diagnostics
Auto Adjust
Operator Page 1
Adaptive
Signal View
Control
Manual SP
Manual Sensor
Configuration
Configuration level
Easy Setup
Device Setup
Display
Control
Input / Output
Communication
Diagnostics
Device Info
Service
Change from one to two columns
Process
display
The process display shows the current process values.
Information
level
The information level contains the parameters and
information that are relevant for the operator. The device
configuration cannot be changed on this level.
Operating
modes menu
In the operating modes menu, the Auto Adjust function
can be started for commissioning purposes. You can
also change the operating modes and switch to the
configuration level.
Configuration
level
The configuration-, parameterization instruction contains
all the parameters required for device commissioning
and configuration. The device configuration can be
changed on this level.
NOTICE – Property damage
During external configuration via a PC, the
positioner no longer responds to the setpoint
current. This may lead to process failures. Prior to
external configuration, always move the actuator
to the safety position and activate manual
adjustment.